ADVFIT AUTOMATION SDN BHD

ADVFIT AUTOMATION SDN BHD
PASSION FOR INDUSTRIAL AUTOMATION | MALAYSIA ,SINGAPORE, THAILAND, INDONESIA, VIETNAM ,PHILIPPINES

Tuesday, July 16, 2013

ZED ZIEGLER ELECTRONIC DEVICES DISTRIBUTION

Components for UV-Systems
  • electronic ballasts for low-pressure and amalgam UV-lamps:
    • electronic ballasts with integrated hour counter and UV-monitoring,
    • electronic ballasts with lamp operation control via RS485,
    • electronic ballasts with adjustable operation parameters,
  • standard and special UV-lamps,
  • control units for UV systems,
  • UV-sensors and UV-monitors for the measurement of relative and absolute uv-intensity, hour counting, status indication...
  • special accessories for measurement technique, e.g. subcontroller for PLC
  • custom-tailored control systems for the domain of water- , air- and process technology
For the special requirements of our customers we offer customized solutions. Our devices show high reliability in world-wide applications. As partners of the manufacturers of systems and devices we are able to respond fast and flexible with our team.

Features  - CONTACT US
  • for use in UV-C monitoring systems
    (for UV values in "%")
  • cost efficient for low budget projects
  • insensitive to daylight
  • photodiode signal
    - external amplification required
                
Installation data
sensitive element: SiC diode
spectral range: 210 - 380nm
(220 - 290nm with UVC filter on request)
operation temperature: 0 - 40°C (32 - 104°F)
max. pressure: 10bar at front (except SiC-SV01-PG)
body material : stainless steel, PTFE (depending on sensor type)
mounting: x001: pipe thread ISO228 G¼ (use MF001-A to adapt to G1)
x003: pipe thread ISO228 G¾
wiring: ready-to-use ZED sensor cables available in several lengths
Features  - CONTACT US
  • for use in UV-C monitoring systems
    (for UV values in "W/m²", "mW/cm²" or "%")
  • one sensor for all applications:
    • low pressure: range 2...500W/m²
    • medium pressure: range 20...3000W/m²
  • fail safe signal transmission regardless of cable length
  • multi sensor operation using one cable by connecting additional sensors to the RS485 bus
                
Installation data
supply voltage: 12...24V DC
sensitive element: SiC diode
spectral range: 210 - 380nm
(220 - 290nm with UVC filter on request)
operation temperature: 0 - 40°C (32 - 104°F)
max. pressure: 10bar at front
body material : stainless steel, PTFE (depending on sensor type)
mounting: x131/x141: pipe thread ISO228 G¼ (use MF001-A to adapt to G1)
x133: pipe thread ISO228 G¾
wiring: ready-to-use ZED sensor cables available in several lengths

Features  - CONTACT US
  • for use in UV-C monitoring systems
    (for UV values in "%")
  • indirect "side-looking" UV-C detection
    - sensor is positioned alongside the lamps
  • for low pressure applications
    - wide intensity range due to automated measuring range selection
  • fail safe signal transmission regardless of cable length
  • multi sensor operation using one cable by connecting additional sensors to the RS485 bus
                
                     
Installation data
supply voltage: 12...24V DC
sensitive element: SiC diode
spectral range: 210 - 380nm
(220 - 290nm with UVC filter on request)
aperture angle: approx. 110° (laterally round)
(220 - 290nm with UVC filter on request)
operation temperature: 0 - 40°C (32 - 104°F)
IP code: IP40
body material : stainless steel (sensor head: PTFE)
mounting: to be mounted in a quartz tube
dimensions: sensor body: Ø20mm x 65mm
sensor head: Ø14mm x 15mm
cable protection tube: Ø8mm x 500mm
wiring: ready-to-use ZED sensor cables available in several lengths
Features  - CONTACT US
  • for use in UV-C monitoring systems
    (for UV values in "W/m²", "mW/cm²" or "%")
  • one sensor for all applications:
    • low pressure: range 2...500W/m²
    • medium pressure: range 20...3000W/m²
    100% reference value for analog signal output can be set by customer using ZCONpro
  • integrated signal converter
  • measurement and display of absolute UV values using ZCONpro
                                
Installation data
supply voltage: 12...24V DC (min. 15V DC for U10 types)
sensitive element: SiC diode
spectral range: 210 - 380nm
(220 - 290nm with UVC filter on request)
operation temperature: 0 - 40°C (32 - 104°F)
max. pressure: 10bar at front
body material : stainless steel, PTFE (depending on sensor type)
mounting: x131/x141: pipe thread ISO228 G¼ (use MF001-A to adapt to G1)
x133: pipe thread ISO228 G¾
wiring: ready-to-use ZED sensor cables available in several lengths


Features    - CONTACT US
  • for use in UV-C monitoring systems
    (for UV values in "W/m²", "mW/cm²" or "%")
  • special adjustment
    depending on respective UV systems
    according to customers specification
  • integrated signal amplifier
                                
Installation data
supply voltage: 12...24V DC (min. 15V DC for U10 types)
sensitive element: SiC diode
spectral range: 210 - 380nm
(220 - 290nm with UVC filter on request)
operation temperature: 0 - 40°C (32 - 104°F)
max. pressure: 10bar at front
body material : stainless steel, PTFE (depending on sensor type)
mounting: x131/x141: pipe thread ISO228 G¼ (use MF001-A to adapt to G1)
x133: pipe thread ISO228 G¾
wiring: ready-to-use ZED sensor cables available in several lengths
Features   -  CONTACT US
  • for use in certified UV-C monitoring systems
  • use D-SiCONORM types as certified UV sensors
  • UV-C intensity measurement in W/m²
    compliant to
    • Austrian standards
      ÖNORM M5873-1 and Vornorm ÖNORM M5873-2
      (sensors are certified by ÖNORM)
    • German standard DVGW W294
    in combination with measurement window MF001
  • one sensor for all applications:
    • low pressure: range 2...500W/m²
    • medium pressure: range 20...3000W/m²
  • fail safe signal transmission regardless of cable length
  • multi sensor operation using one cable
    by connecting additional sensors to the RS485 bus
                
Installation data
supply voltage: 12...24V DC
sensitive element: SiC diode
spectral range: 210 - 290nm
operation temperature: 0 - 40°C (32 - 104°F)
max. pressure: 10bar on using with measurement window MF001
(not waterproof without MF001
body material: stainless steel
mounting: use with MF001
(MF001: pipe thread ISO228 G1)
wiring: ready-to-use ZED sensor cables available in several lengths


CONTACT US
 

No comments: